TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE B: GENERAL PROVISIONS CHAPTER I: POLLUTION CONTROL BOARD SUBCHAPTER c: EMISSION STANDARDS AND LIMITATIONS FOR STATIONARY SOURCES PART 229 HOSPITAL/MEDICAL/INFECTIOUS WASTE INCINERATORS SECTION 229.158 VIOLATIONS BY HMIWIS EQUIPPED WITH A DRY SCRUBBER FOLLOWED BY A FABRIC FILTER AND A WET SCRUBBER
Section 229.158 Violations by HMIWIs Equipped with a Dry Scrubber Followed by a Fabric Filter and a Wet Scrubber
Except as provided in Section 229.164 of this Subpart, for an HMIWI equipped with a dry scrubber followed by a fabric filter and a wet scrubber:
a) Simultaneous operation of an HMIWI above the maximum charge rate and below the minimum secondary chamber temperature (each measured on a 3-hour rolling average) is a violation of the CO emission limit;
b) Simultaneous operation of an HMIWI above the maximum fabric filter inlet temperature, above the maximum charge rate and below the minimum dioxin/furan sorbent flow rate (each measured on a 3-hour rolling average) is a violation of the dioxin/furan emission limit;
c) Simultaneous operation of an HMIWI above the maximum charge rate and below the minimum scrubber liquor pH (each measured on a 3-hour rolling average) is a violation of the HCl emission limit;
d) Simultaneous operation of an HMIWI above the maximum charge rate and below the minimum Hg sorbent flow rate (each measured on a 3-hour rolling average) is a violation of the Hg emission limit; or
e) Use of the bypass stack (except during startup, shutdown, or malfunction) is a violation of the PM, dioxin/furan, HCl, Pb, Cd and Hg emission limits. |