TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE B: GENERAL PROVISIONS
CHAPTER I: POLLUTION CONTROL BOARD
SUBCHAPTER c: EMISSION STANDARDS AND LIMITATIONS FOR STATIONARY SOURCES
PART 229 HOSPITAL/MEDICAL/INFECTIOUS WASTE INCINERATORS
SECTION 229.158 VIOLATIONS BY HMIWIS EQUIPPED WITH A DRY SCRUBBER FOLLOWED BY A FABRIC FILTER AND A WET SCRUBBER


 

Section 229.158  Violations by HMIWIs Equipped with a Dry Scrubber Followed by a Fabric Filter and a Wet Scrubber

 

Except as provided in Section 229.164 of this Subpart, for an HMIWI equipped with a dry scrubber followed by a fabric filter and a wet scrubber:

 

a)         Simultaneous operation of an HMIWI above the maximum charge rate and below the minimum secondary chamber temperature (each measured on a 3-hour rolling average) is a violation of the CO emission limit;

 

b)         Simultaneous operation of an HMIWI above the maximum fabric filter inlet temperature, above the maximum charge rate and below the minimum dioxin/furan sorbent flow rate (each measured on a 3-hour rolling average) is a violation of the dioxin/furan emission limit;

 

c)         Simultaneous operation of an HMIWI above the maximum charge rate and below the minimum scrubber liquor pH (each measured on a 3-hour rolling average) is a violation of the HCl emission limit;

 

d)         Simultaneous operation of an HMIWI above the maximum charge rate and below the minimum Hg sorbent flow rate (each measured on a 3-hour rolling average) is a violation of the Hg emission limit; or

 

e)         Use of the bypass stack (except during startup, shutdown, or malfunction) is a violation of the PM, dioxin/furan, HCl, Pb, Cd and Hg emission limits.