TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE B: GENERAL PROVISIONS
CHAPTER I: POLLUTION CONTROL BOARD
SUBCHAPTER c: EMISSION STANDARDS AND LIMITATIONS FOR STATIONARY SOURCES
PART 229 HOSPITAL/MEDICAL/INFECTIOUS WASTE INCINERATORS
SECTION 229.APPENDIX B OPERATING PARAMETERS TO BE MONITORED AND MINIMUM MEASUREMENT AND RECORDING FREQUENCIES



Section 229.APPENDIX B   Operating Parameters to be Monitored and Minimum Measurement and Recording Frequencies

 

An "X" in any box in this matrix means that measurement of that parameter is required.

 

MINIMUM FREQUENCY

CONTROL SYSTEM

Operating Parameters

Data Measurement

Data Recording

Dry Scrubber Followed by Fabric Filter

Wet Scrubber

Dry Scrubber Followed by Fabric Filter and Wet Scrubber

Maximum1 Charge Rate

Continuous

Once per hour

X

X

X

Maximum Fabric Filter Inlet Temperature

Continuous

Once per minute

X

 

X

Maximum flue gas temperature

Continuous

Once per minute

X

X

 

Minimum secondary chamber temperature

Continuous

Once per minute

X

X

X

Minimum Dioxin/Furan Sorbent Flow Rate

Hourly

Once per hour

X

 

X

Minimum HCl Sorbent Flow Rate

Hourly

Once per hour

X

 

X

Minimum Hg Sorbent Flow Rate

Hourly

Once per hour

X

 

X

Minimum Pressure Drop Across the Wet Scrubber or Minimum Horsepower or Amperage to Wet Scrubber

Continuous

Once per minute

 

X

X

Minimum Scrubber Liquor Flow Rate

Continuous

Once per minute

 

X

X

Minimum Scrubber Liquor pH

Continuous

Once per minute

 

X

X

 

1For batch HMIWIs, record the charge per batch.