TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE F: PUBLIC WATER SUPPLIES CHAPTER I: POLLUTION CONTROL BOARD PART 611 PRIMARY DRINKING WATER STANDARDS SECTION 611.1014 TREATMENT TECHNIQUE REQUIREMENTS: REQUIREMENTS FOR UNCOVERED FINISHED WATER STORAGE FACILITIES
Section 611.1014 Treatment Technique Requirements: Requirements for Uncovered Finished Water Storage Facilities
a) A supplier that uses uncovered finished water storage facilities must comply with the conditions of this Section.
b) A supplier must notify the Agency in writing of the use of each uncovered finished water storage facility.
c) A supplier must meet either of the following conditions for each uncovered finished water storage facility, or the supplier must comply with an Agency-approved schedule to meet these conditions:
1) The supplier must cover any uncovered finished water storage facility; or
2) The supplier must treat the discharge from the uncovered finished water storage facility to the distribution system to achieve inactivation or removal of at least 4-log virus, 3-log Giardia lamblia, and 2-log Cryptosporidium using a protocol approved by the Agency.
d) A failure to comply with the requirements of this Section is a violation of the treatment technique requirement.
BOARD NOTE: Derived from 40 CFR 141.714 (2016).
(Source: Amended at 42 Ill. Reg. 1140, effective January 4, 2018) |