TITLE 41: FIRE PROTECTION
CHAPTER I: OFFICE OF THE STATE FIRE MARSHAL
PART 160 STORAGE, TRANSPORTATION, SALE AND USE OF GASOLINE AND VOLATILE OILS: RULES AND REGULATIONS\ RELATING TO GENERAL STORAGE
SECTION 160.40 LOCATION OF TANKS – DISTANCE BETWEEN ABOVEGROUND TANKS


 

Section 160.40  Location of Tanks – Distance Between Aboveground Tanks

 

a)         The minimum distance from tanks to adjacent tanks shall be as follows:

 

Tank Capacity

(Gallons)

Minimum Distance

(Feet)

 

24,000 or less.................................................

5

 

24,001 to 48,000............................................

10

 

48,001 to 75,000............................................

13

 

75,001 to 100,000..........................................

15

 

Over 100,000.................................................

One Tank Diameter

 

b)         If tanks are of different capacities, the capacity of the larger tank shall govern its distance to adjacent tanks.

 

c)         Existing tanks of under 24,000 gallons shall maintain a minimum distance of at least 3 feet.

 

(Source:  Amended at 9 Ill. Reg. 10012, effective October 1, 1985)