TITLE 77: PUBLIC HEALTH
CHAPTER I: DEPARTMENT OF PUBLIC HEALTH
SUBCHAPTER c: LONG-TERM CARE FACILITIES
PART 300 SKILLED NURSING AND INTERMEDIATE CARE FACILITIES CODE
SECTION 300.TABLE B PRESSURE RELATIONSHIPS AND VENTILATION RATES OF CERTAIN AREAS FOR NEW INTERMEDIATE CARE FACILITIES AND SKILLED NURSING FACILITIES



Section 300.TABLE B   Pressure Relationships and Ventilation Rates of Certain Areas for New Intermediate Care Facilities and Skilled Nursing Facilities

 

Area

Designation

Pressure Relationship to Adjacent Areas

Minimum Air Changes Per Hour Supplied To Room

All Air Exhausted Directly Outdoors

Recirculated within Room Units

Resident Rm

0

2

Optional

Optional

Medication Rm.

+

4

Optional

Optional

Clean Utility Rm.

+

4

Optional

Optional

Clean Linen Storage

+

2

Optional

Optional

Examination and Treatment Rm.

0

2

Optional

Optional

Physical Therapy

-

4

Optional

Optional

Occupational Therapy

-

2

Optional

Optional

Dietary Day Storage

0

2

Optional

No

Soiled Utility

-

6

Yes

No

Soiled Linen Holding Rm.

-

6

Yes

No

Soiled Linen & Trash Chute Rm.

-

6

Yes

No

Toilet Rm.

-

6

Yes

No

Shower Rm.

-

6

Yes

No

Bathroom

-

6

Yes

No

Janitors' Closet

-

6

Yes

No

Food Preparation Areas

0

6

Yes

No

Dishwashing

-

6

Yes

No

Laundry, General

0

6

Yes

No

Soiled Linen Sorting & Storage

-

6

Yes

No

 

 

 

 

 

 

 

 

 

 

+

=

Positive

 

 

-

=

Negative

 

 

0

=

Equal

 

 

 

 

The ventilation rates shown in the above TABLE shall be considered as minimum acceptable rates and shall not be construed as precluding the use of higher ventilation rates.