TITLE 32: ENERGY
CHAPTER II: ILLINOIS EMERGENCY MANAGEMENT AGENCY
SUBCHAPTER b: RADIATION PROTECTION
PART 346 LICENSES AND RADIATION SAFETY REQUIREMENTS FOR IRRADIATORS
SECTION 346.630 POOL WATER PURITY


 

Section 346.630  Pool Water Purity

 

a)         Pool water purification system shall be run sufficiently to maintain the conductivity of the pool water below 20 microsiemens per centimeter under normal circumstances.  If pool water conductivity rises above 20 microsiemens per centimeter, the licensee shall take prompt actions to lower the pool water conductivity and shall take corrective actions to prevent future recurrences.

 

b)         The licensee shall measure the pool water conductivity frequently enough, but no less than weekly, to assure that the conductivity remains below 20 microsiemens per centimeter.  Conductivity meters shall be calibrated at least annually.