TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE B: AIR POLLUTION CHAPTER I: POLLUTION CONTROL BOARD SUBCHAPTER c: EMISSIONS STANDARDS AND LIMITATIONS FOR STATIONARY SOURCES PART 218 ORGANIC MATERIAL EMISSION STANDARDS AND LIMITATIONS FOR THE CHICAGO AREA SECTION 218.488 MONITORING FOR AIR POLLUTION CONTROL EQUIPMENT
Section 218.488 Monitoring for Air Pollution Control Equipment
a) At a minimum, continuous monitors for the following parameters shall be installed on air pollution control equipment used to control sources subject to this Subpart:
1) Destruction device combustion temperature.
2) Temperature rise across a catalytic afterburner bed.
3) VOM concentration on a carbon adsorption unit to determine breakthrough.
4) Outlet gas temperature of a refrigerated condenser.
5) Temperature of a non-refrigerated condenser coolant supply system.
b) Each monitor shall be equipped with a recording device.
c) Each monitor shall be calibrated quarterly.
d) Each monitor shall operate at all times while the associated control equipment is operating. |