Section 250.TABLE G Insulation/Building
Perimeter
1) Zones for insulation/building perimeter requirements shall
consist of the counties listed here.
Zone 1 includes the following
counties:
|
Boone
|
Ford
|
Kane
|
Lee
|
Ogle
|
Tazewell
|
Bureau
|
Grundy
|
Kankakee
|
Livingston
|
Peoria
|
Warren
|
Carroll
|
Henderson
|
Kendall
|
Marshall
|
Putnam
|
Whiteside
|
Cook
|
Henry
|
Knox
|
McHenry
|
Rock Island
|
Will
|
DeKalb
|
Iroquois
|
Lake
|
McLean
|
Stark
|
Winnebago
|
DuPage
|
JoDaviess
|
LaSalle
|
Mercer
|
Stephenson
|
Woodford
|
Zone 2 includes the following
counties:
|
Adams
|
Clark
|
Effingham
|
Jersey
|
McDonough
|
Pike
|
Bond
|
Coles
|
Fayette
|
Logan
|
Menard
|
Sangamon
|
Brown
|
Crawford
|
Fulton
|
Macon
|
Montgomery
|
Schuyler
|
Calhoun
|
Cumberland
|
Greene
|
Macoupin
|
Morgan
|
Scott
|
Cass
|
DeWitt
|
Hancock
|
Madison
|
Moultrie
|
Shelby
|
Champaign
|
Douglas
|
Jasper
|
Mason
|
Piatt
|
Vermilion
|
Christian
|
Edgar
|
Zone 3 includes the following
counties:
|
Alexander
|
Gallatin
|
Johnson
|
Perry
|
St. Clair
|
Washington
|
Clay
|
Hamilton
|
Lawrence
|
Pope
|
Saline
|
Wayne
|
Clinton
|
Hardin
|
Marion
|
Pulaski
|
Union
|
White
|
Edwards
|
Jackson
|
Massac
|
Randolph
|
Wabash
|
Williamson
|
Franklin
|
Jefferson
|
Monroe
|
Richland
|
2) The following minimum building perimeter insulation R values
shall be provided:
|
Roof
|
Walls
|
Floors
|
Zone 1
|
R-20
|
R-17
|
R-19
|
Zone 2
|
R-18
|
R-17
|
R-19
|
Zone 3
|
R-15
|
R-12
|
R-11
|
3) All windows shall be glazed with double glazed insulating
glass. All exterior windows and door frames shall be constructed of non-cold
conducting materials such as wood or metal with a thermal break.
(Source: Amended at 12 Ill. Reg. 15080, effective October 1, 1988)