TITLE 77: PUBLIC HEALTH
CHAPTER I: DEPARTMENT OF PUBLIC HEALTH
SUBCHAPTER r: WATER AND SEWAGE
PART 920 WATER WELL CONSTRUCTION CODE
SECTION 920.TABLE A STEEL CASING AND LINER PIPE WEIGHTS AND DIMENSIONS



Section 920.TABLE A   Steel Casing and Liner Pipe Weights and Dimensions

 

SIZE

 

DIAMETER (in.)

 

THICKNESS

 

WEIGHT (lbs. per ft.)

in.

 

External

Internal

 

in.

 

Plain ends (calculated)

With threads and couplings (nominal)

1

 

1.315

1.049

 

0.133

 

1.68

1.70

 

1.660

1.380

 

0.140

 

2.27

2.30

 

1.900

1.610

 

0.145

 

2.72

2.75

2

 

2.375

2.067

 

0.154

 

3.65

3.75

 

2.875

2.469

 

0.203

 

5.79

5.90

3

 

3.500

3.068

 

0.216

 

7.58

7.70

 

4.000

3.548

 

0.226

 

9.11

9.25

4

 

4.500

4.026

 

0.237

 

10.79

11.00

5

 

5.563

5.047

 

0.258

 

14.62

15.00

6

 

6.625

6.065

 

0.280

 

18.97

19.45

8

 

8.625

8.071

 

0.277

 

24.70

25.55

10

 

10.750

10.136

 

0.307

 

34.24

35.75

12

 

12.750

12.090

 

0.330

 

43.77

45.45

14

 

14.000

13.250

 

0.375

 

54.57

57.00

16

 

16.000

15.250

 

0.375

 

62.58

65.30

18

 

18.000

17.250

 

0.375

 

70.59

73.00

20

 

20.000

19.250

 

0.375

 

78.60

81.00

 

Pipe sizes not listed that are less than 8 inches in diameter shall be Schedule 40 pipe as a minimum.

 

Pipe sizes not listed that are 8 inches in diameter or greater shall be Schedule 30 pipe as a minimum.

 

Pipes for driven wells shall be Schedule 40 as a minimum.

 

(Source:  Amended at 18 Ill. Reg. 17684, effective November 30, 1994)