a)         The accuracy of a water meter shall be tested by comparing the actual amount of water passing through it with the amount indicated on the dial.

 

b)         The test shall be conducted in accordance with the standards for testing Cold Water Meters as prescribed by the American Water Works Association (AWWA C705-60) with quantities and flows for positive displacement meters as follows:

 

TEST FLOWS (G.P.M.) & QUANTITY

 

MINIMUM

INTERMEDIATE

MAXIMUM

Size of

Flow

QUANTITY

FLOW

QUANTITY

FLOW

QUANTITY

meter

G.P.M.

Gal.

Cu.Ft.

G.P.M.

Gal.

Cu.Ft.

G.P.M.

Gal.

Cu.Ft.

⅝"

¼

10

1

2

10

1

15

100

10

¾"

½

10

1

3

10

1

25

100

10

1"

¾

10

1

4

10

1

40

100

10

1½"

100

10

8

100

10

80

1000

100

2"

2

100

10

15

100

10

120

1000

100

3"

4

100

10

20

100

10

250

1000

100

4"

7

100

10

40

100

10

350

1000

100

6"

12

100

10

60

100

10

700

1000

100

 

No meters shall be placed in service when the accuracy is different than follows:

 

 

NEW METERS

REPAIRED METERS

MINIMUM RANGE

95-101.5%

90-101.5%

INTERMEDIATE RANGE

98.5-101.5%

98.5-101.5%

MAXIMUM RANGE

98.5-101.5%

98.5-101.5%

 

c)         The utility may make such additional tests as it may deem necessary but in a manner that will not unreasonably inconvenience the customer.