| 1 | | American National Standards Institute. |
| 2 | | (2) Inspectors shall certify that the all fire and |
| 3 | | smoke dampers inspected comply with Section 717 of the 2012 |
| 4 | | International Building Code. |
| 5 | | (3) All tests shall be completed safely by personnel |
| 6 | | wearing protective equipment. |
| 7 | | (4) Unobstructed access to fire and smoke dampers shall |
| 8 | | be verified and corrected as required. |
| 9 | | (5) Fire and smoke dampers shall be actuated and cycled |
| 10 | | as a part of the associated smoke detector testing in |
| 11 | | accordance with the National Fire Alarm and Signaling Code |
| 12 | | of the National Fire Protection Association. |
| 13 | | (6) If fire and smoke dampers have a fusible link, the |
| 14 | | link shall be removed for testing to ensure full closure |
| 15 | | and lock-in-place, if so equipped. |
| 16 | | (7) The operation test of fire and smoke dampers shall |
| 17 | | verify that there is no interference concerning the fire |
| 18 | | and smoke damper due to rusted, bent, misaligned, or |
| 19 | | damaged frames or blades or defective hinges or parts. |
| 20 | | (8) Fire and smoke damper frames shall not be |
| 21 | | penetrated by any foreign objects that would affect fire |
| 22 | | and smoke damper operations. |
| 23 | | (9) Fire and smoke dampers shall not be blocked from |
| 24 | | closure in any way. |
| 25 | | (10) Fusible links, if applicable, shall be |
| 26 | | reinstalled after the completion of testing. |
|
| | SB2563 | - 3 - | LRB101 17832 CPF 67266 b |
|
|
| 1 | | (11) If fusible links are damaged or painted, they |
| 2 | | shall be replaced with a link of the same size, |
| 3 | | temperature, and load rating. |
| 4 | | (12) All inspections and testing shall include |
| 5 | | documentation stating the location of the fire and smoke |
| 6 | | damper, the date of the inspection, the name of the |
| 7 | | inspector, and any deficiencies discovered. The |
| 8 | | documentation shall have a designated space to indicate |
| 9 | | when and how the deficiencies, if any, were corrected. All |
| 10 | | documentation shall be maintained and made available for |
| 11 | | review at the request of the unit of local government |
| 12 | | having jurisdiction over the building receiving the |
| 13 | | inspection and testing.
|
| 14 | | Section 99. Effective date. This Act takes effect upon |
| 15 | | becoming law.
|