| AN ACT concerning fire safety.
|
| 2 |
| Be it enacted by the People of the State of Illinois,
|
| 3 |
| represented in the General Assembly:
|
| 4 |
| Section 5. The Public Building Egress Act is amended by |
| 5 |
| adding Section 1.5 as follows: |
| 6 |
| (425 ILCS 55/1.5 new)
|
| 7 |
| Sec. 1.5. Stairwell door access. |
| 8 |
| (a) Stairwell enclosures in buildings greater than 4 |
| 9 |
| stories shall comply with one of the following requirements: |
| 10 |
| (1) No stairwell enclosure door shall be locked at any |
| 11 |
| time in order to provide re-entry from the stair enclosure |
| 12 |
| to the interior of the building; or |
| 13 |
| (2) Stairwell enclosure doors that are locked shall be |
| 14 |
| equipped with an electronic lock release system that is |
| 15 |
| activated upon loss of power, manually by a single switch |
| 16 |
| accessible to building management or firefighting |
| 17 |
| personnel, and automatically by activation of the |
| 18 |
| building's fire alarm system. |
| 19 |
| A telephone or other two-way communications system |
| 20 |
| connected to an approved constantly attended location shall be |
| 21 |
| provided at not less than every fifth floor in each stairway |
| 22 |
| where the doors to the stairway are locked. If this option is |
| 23 |
| selected, the building must comply with these requirements by |
| 24 |
| January 1, 2005. |
| 25 |
| (b) Regardless of which option is selected under subsection |
| 26 |
| (a), stairwell enclosure doors at the main egress level of the |
| 27 |
| building shall remain unlocked from the stairwell enclosure |
| 28 |
| side at all times. |
| 29 |
| (c) Building owners that select the option under paragraph |
| 30 |
| (2) of subsection (a) must comply with the following |
| 31 |
| requirements during the time necessary to install a lock |
| 32 |
| release system and the two-way communication system: |