|
|||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||
| |||||||||||||||||||||||||||
| |||||||||||||||||||||||||||
| |||||||||||||||||||||||||||
1 | AN ACT concerning safety.
| ||||||||||||||||||||||||||
2 | Be it enacted by the People of the State of Illinois,
| ||||||||||||||||||||||||||
3 | represented in the General Assembly:
| ||||||||||||||||||||||||||
4 | Section 5. The Facilities Requiring Smoke Detectors Act is | ||||||||||||||||||||||||||
5 | amended by changing Section 2 as follows:
| ||||||||||||||||||||||||||
6 | (425 ILCS 10/2) (from Ch. 127 1/2, par. 822)
| ||||||||||||||||||||||||||
7 | Sec. 2.
(a) Every facility shall be equipped with at least | ||||||||||||||||||||||||||
8 | one
approved smoke detector in an operating condition within 15 | ||||||||||||||||||||||||||
9 | feet of every room
used for sleeping purposes. The detector | ||||||||||||||||||||||||||
10 | shall be installed on the ceiling
and at least 6 inches from | ||||||||||||||||||||||||||
11 | any wall, or on a wall located between 4 and 6
inches from the | ||||||||||||||||||||||||||
12 | ceiling.
| ||||||||||||||||||||||||||
13 | (b) Every facility shall have at least one approved smoke | ||||||||||||||||||||||||||
14 | detector installed on
every story of the facility, including | ||||||||||||||||||||||||||
15 | basements but not including
unoccupied attics; provided that | ||||||||||||||||||||||||||
16 | there shall be at least one detector at
the beginning and at | ||||||||||||||||||||||||||
17 | the end of each separate corridor or hallway 200 feet
or more | ||||||||||||||||||||||||||
18 | in length in any occupied story, including basements.
| ||||||||||||||||||||||||||
19 | (c) Every facility shall have at least
one
approved smoke | ||||||||||||||||||||||||||
20 | detector at the uppermost ceiling of
each interior stairwell, | ||||||||||||||||||||||||||
21 | except in fire resistive structures. The detector
shall be | ||||||||||||||||||||||||||
22 | installed on the ceiling,
at least 6 inches from the wall, or | ||||||||||||||||||||||||||
23 | on a wall located between 4 and 6
inches from the ceiling.
|
| |||||||
| |||||||
1 | (d) The requirements of this Section shall apply to any | ||||||
2 | facility
in existence on July 1, 1988, beginning on that date. | ||||||
3 | Except as provided
in subsection (e), the smoke
detectors | ||||||
4 | required in such facilities may be either battery powered or
| ||||||
5 | wired into the structure's AC power line, and need not be | ||||||
6 | interconnected.
| ||||||
7 | (e) In the case of any facility unit that is newly | ||||||
8 | constructed,
reconstructed or substantially remodelled after | ||||||
9 | December 31, 1987, the
requirements of this Section shall apply | ||||||
10 | beginning on the first day of
occupancy of the facility after | ||||||
11 | such construction, reconstruction or
substantial remodelling. | ||||||
12 | The smoke detectors required in such facility
shall be | ||||||
13 | permanently wired into the structure's AC power line and, if
| ||||||
14 | more than one detector is required to be installed within the | ||||||
15 | facility,
the detectors shall be wired so that the actuation of | ||||||
16 | one detector will
actuate all the detectors in the facility | ||||||
17 | unit. | ||||||
18 | In the case of any facility unit that is newly constructed,
| ||||||
19 | reconstructed, or substantially remodeled on or after January | ||||||
20 | 1, 2011, smoke detectors permanently wired into the structure's | ||||||
21 | AC power line must also maintain an alternative back-up battery | ||||||
22 | power source.
| ||||||
23 | (f) Compliance with an applicable federal, State or local | ||||||
24 | law, rule or
building code which requires the installation and | ||||||
25 | maintenance of smoke
detectors in a manner different from this | ||||||
26 | Section, but providing a level of
safety for occupants which is |
| |||||||
| |||||||
1 | equal to or greater than that provided by
this Section, shall | ||||||
2 | be deemed to be compliance with this Section, and the | ||||||
3 | requirements of
such more stringent law shall govern over the | ||||||
4 | requirements of this Section.
| ||||||
5 | (g) In
the case of a
facility subject to this Act, the | ||||||
6 | provisions of this Act shall be enforced
by the State agency | ||||||
7 | which licenses that facility.
The State licensing agency may | ||||||
8 | suspend the
facility's license for a violation of this Act | ||||||
9 | where appropriate.
| ||||||
10 | (Source: P.A. 85-936.)
| ||||||
11 | Section 10. The Smoke Detector Act is amended by changing | ||||||
12 | Section 3 as follows:
| ||||||
13 | (425 ILCS 60/3) (from Ch. 127 1/2, par. 803)
| ||||||
14 | Sec. 3.
(a) Every dwelling unit shall be equipped with at | ||||||
15 | least one
approved smoke detector in an operating condition | ||||||
16 | within 15 feet of every room
used for sleeping purposes. The | ||||||
17 | detector shall be installed on the ceiling
and at least 6 | ||||||
18 | inches from any wall, or on a wall located between 4 and 6
| ||||||
19 | inches from the ceiling.
| ||||||
20 | (b) Every single family residence shall have at least one | ||||||
21 | approved smoke
detector installed on every story of the | ||||||
22 | dwelling unit, including basements
but not including | ||||||
23 | unoccupied attics. In dwelling units with split levels,
a smoke | ||||||
24 | detector installed on the upper level shall suffice for the
|
| |||||||
| |||||||
1 | adjacent lower level if the lower level is less than one full | ||||||
2 | story below
the upper level; however, if there is an | ||||||
3 | intervening door between the
adjacent levels, a smoke detector | ||||||
4 | shall be installed on each level.
| ||||||
5 | (c) Every structure which (1) contains more than one | ||||||
6 | dwelling unit, or
(2) contains at least one dwelling unit and | ||||||
7 | is a mixed-use structure, shall
contain at least one approved | ||||||
8 | smoke detector at the uppermost ceiling of
each interior | ||||||
9 | stairwell. The detector shall be installed on the ceiling,
at | ||||||
10 | least 6 inches from the wall, or on a wall located between 4 | ||||||
11 | and 6
inches from the ceiling.
| ||||||
12 | (d) It shall be the responsibility of the owner of a | ||||||
13 | structure to supply
and install all required detectors. The | ||||||
14 | owner shall be responsible for
making reasonable efforts to | ||||||
15 | test and maintain detectors in common
stairwells and hallways. | ||||||
16 | It shall be the responsibility of a tenant to
test and to | ||||||
17 | provide general maintenance for the detectors within the
| ||||||
18 | tenant's dwelling unit or rooming unit, and to notify the owner | ||||||
19 | or the
authorized agent of the owner in writing of any | ||||||
20 | deficiencies which the
tenant cannot correct. The owner shall | ||||||
21 | be responsible for providing one
tenant per dwelling unit with | ||||||
22 | written information regarding detector
testing and | ||||||
23 | maintenance.
| ||||||
24 | The tenant shall be responsible for replacement of any | ||||||
25 | required batteries
in the smoke detectors in the tenant's | ||||||
26 | dwelling unit, except that the owner
shall ensure that such |
| |||||||
| |||||||
1 | batteries are in operating condition at the time
the tenant | ||||||
2 | takes possession of the dwelling unit. The tenant shall provide
| ||||||
3 | the owner or the authorized agent of the owner with access to | ||||||
4 | the dwelling
unit to correct any deficiencies in the smoke | ||||||
5 | detector which have been
reported in writing to the owner or | ||||||
6 | the authorized agent of the owner.
| ||||||
7 | (e) The requirements of this Section shall apply to any | ||||||
8 | dwelling unit
in existence on July 1, 1988, beginning on that | ||||||
9 | date. Except as provided
in subsections (f) and (g), the smoke | ||||||
10 | detectors required in such dwelling
units may be either battery | ||||||
11 | powered or wired into the structure's AC power
line, and need | ||||||
12 | not be interconnected.
| ||||||
13 | (f) In the case of any dwelling unit that is newly | ||||||
14 | constructed,
reconstructed, or substantially remodelled after | ||||||
15 | December 31, 1987, the
requirements of this Section shall apply | ||||||
16 | beginning on the first day of
occupancy of the dwelling unit | ||||||
17 | after such construction, reconstruction or
substantial | ||||||
18 | remodelling. The smoke detectors required in such dwelling
unit | ||||||
19 | shall be permanently wired into the structure's AC power line, | ||||||
20 | and if
more than one detector is required to be installed | ||||||
21 | within the dwelling
unit, the detectors shall be wired so that | ||||||
22 | the actuation of one detector
will actuate all the detectors in | ||||||
23 | the dwelling unit.
| ||||||
24 | In the case of any dwelling unit that is newly constructed,
| ||||||
25 | reconstructed, or substantially remodeled on or after January | ||||||
26 | 1, 2011, smoke detectors permanently wired into the structure's |
| |||||||
| |||||||
1 | AC power line must also maintain an alternative back-up battery | ||||||
2 | power source. | ||||||
3 | (g) Every hotel shall be equipped with operational portable
| ||||||
4 | smoke-detecting alarm devices for the deaf and hearing impaired | ||||||
5 | of audible
and visual design, available for units of occupancy.
| ||||||
6 | Specialized smoke-detectors for the deaf and hearing | ||||||
7 | impaired shall be
available upon request by guests in such | ||||||
8 | hotels at a rate
of at least one such smoke detector per 75 | ||||||
9 | occupancy units or portions
thereof, not to exceed 5 such smoke | ||||||
10 | detectors per hotel.
Incorporation or connection into an | ||||||
11 | existing interior alarm system, so as
to be capable of being | ||||||
12 | activated by the system, may be utilized in lieu of
the | ||||||
13 | portable alarms.
| ||||||
14 | Operators of any hotel shall post conspicuously at the main | ||||||
15 | desk a
permanent notice, in letters at least 3 inches in | ||||||
16 | height, stating that
smoke detector alarm devices for the deaf | ||||||
17 | and hearing impaired are
available. The proprietor may require | ||||||
18 | a refundable deposit for a portable
smoke detector not to | ||||||
19 | exceed the cost of the detector.
| ||||||
20 | (h) Compliance with an applicable federal, State or local | ||||||
21 | law or
building code which requires the installation and | ||||||
22 | maintenance of smoke
detectors in a manner different from this | ||||||
23 | Section, but providing a level of
safety for occupants which is | ||||||
24 | equal to or greater than that provided by
this Section, shall | ||||||
25 | be deemed to be in compliance with this Section, and
the | ||||||
26 | requirements of such more stringent law shall govern over the
|
| |||||||
| |||||||
1 | requirements of this Section.
| ||||||
2 | (Source: P.A. 85-1404.)
| ||||||
3 | Section 99. Effective date. This Act takes effect January | ||||||
4 | 1, 2011.
|