| AN ACT concerning safety.
|
2 |
| Be it enacted by the People of the State of Illinois,
|
3 |
| represented in the General Assembly:
|
4 |
| Section 5. The Facilities Requiring Smoke Detectors Act is |
5 |
| amended by changing Section 2 as follows:
|
6 |
| (425 ILCS 10/2) (from Ch. 127 1/2, par. 822)
|
7 |
| Sec. 2.
(a) Every facility shall be equipped with at least |
8 |
| one
approved smoke detector in an operating condition within 15 |
9 |
| feet of every room
used for sleeping purposes. The detector |
10 |
| shall be installed on the ceiling
and at least 6 inches from |
11 |
| any wall, or on a wall located between 4 and 6
inches from the |
12 |
| ceiling.
|
13 |
| (b) Every facility shall have at least one approved smoke |
14 |
| detector installed on
every story of the facility, including |
15 |
| basements but not including
unoccupied attics; provided that |
16 |
| there shall be at least one detector at
the beginning and at |
17 |
| the end of each separate corridor or hallway 200 feet
or more |
18 |
| in length in any occupied story, including basements.
|
19 |
| (c) Every facility shall have at least
one
approved smoke |
20 |
| detector at the uppermost ceiling of
each interior stairwell, |
21 |
| except in fire resistive structures. The detector
shall be |
22 |
| installed on the ceiling,
at least 6 inches from the wall, or |
23 |
| on a wall located between 4 and 6
inches from the ceiling.
|
|
|
|
HB5821 Engrossed |
- 2 - |
LRB096 20660 DRJ 36377 b |
|
|
1 |
| (d) The requirements of this Section shall apply to any |
2 |
| facility
in existence on July 1, 1988, beginning on that date. |
3 |
| Except as provided
in subsection (e), the smoke
detectors |
4 |
| required in such facilities may be either battery powered or
|
5 |
| wired into the structure's AC power line, and need not be |
6 |
| interconnected.
|
7 |
| (e) In the case of any facility unit that is newly |
8 |
| constructed,
reconstructed or substantially remodelled after |
9 |
| December 31, 1987, the
requirements of this Section shall apply |
10 |
| beginning on the first day of
occupancy of the facility after |
11 |
| such construction, reconstruction or
substantial remodelling. |
12 |
| The smoke detectors required in such facility
shall be |
13 |
| permanently wired into the structure's AC power line and, if
|
14 |
| more than one detector is required to be installed within the |
15 |
| facility,
the detectors shall be wired so that the actuation of |
16 |
| one detector will
actuate all the detectors in the facility |
17 |
| unit. |
18 |
| In the case of any facility unit that is newly constructed,
|
19 |
| reconstructed, or substantially remodeled on or after January |
20 |
| 1, 2011, smoke detectors permanently wired into the structure's |
21 |
| AC power line must also maintain an alternative back-up power |
22 |
| source, which may be either a battery or batteries or an |
23 |
| emergency generator.
|
24 |
| (f) Compliance with an applicable federal, State or local |
25 |
| law, rule or
building code which requires the installation and |
26 |
| maintenance of smoke
detectors in a manner different from this |
|
|
|
HB5821 Engrossed |
- 3 - |
LRB096 20660 DRJ 36377 b |
|
|
1 |
| Section, but providing a level of
safety for occupants which is |
2 |
| equal to or greater than that provided by
this Section, shall |
3 |
| be deemed to be compliance with this Section, and the |
4 |
| requirements of
such more stringent law shall govern over the |
5 |
| requirements of this Section.
|
6 |
| (g) In
the case of a
facility subject to this Act, the |
7 |
| provisions of this Act shall be enforced
by the State agency |
8 |
| which licenses that facility.
The State licensing agency may |
9 |
| suspend the
facility's license for a violation of this Act |
10 |
| where appropriate.
|
11 |
| (Source: P.A. 85-936.)
|
12 |
| Section 10. The Smoke Detector Act is amended by changing |
13 |
| Section 3 as follows:
|
14 |
| (425 ILCS 60/3) (from Ch. 127 1/2, par. 803)
|
15 |
| Sec. 3.
(a) Every dwelling unit shall be equipped with at |
16 |
| least one
approved smoke detector in an operating condition |
17 |
| within 15 feet of every room
used for sleeping purposes. The |
18 |
| detector shall be installed on the ceiling
and at least 6 |
19 |
| inches from any wall, or on a wall located between 4 and 6
|
20 |
| inches from the ceiling.
|
21 |
| (b) Every single family residence shall have at least one |
22 |
| approved smoke
detector installed on every story of the |
23 |
| dwelling unit, including basements
but not including |
24 |
| unoccupied attics. In dwelling units with split levels,
a smoke |
|
|
|
HB5821 Engrossed |
- 4 - |
LRB096 20660 DRJ 36377 b |
|
|
1 |
| detector installed on the upper level shall suffice for the
|
2 |
| adjacent lower level if the lower level is less than one full |
3 |
| story below
the upper level; however, if there is an |
4 |
| intervening door between the
adjacent levels, a smoke detector |
5 |
| shall be installed on each level.
|
6 |
| (c) Every structure which (1) contains more than one |
7 |
| dwelling unit, or
(2) contains at least one dwelling unit and |
8 |
| is a mixed-use structure, shall
contain at least one approved |
9 |
| smoke detector at the uppermost ceiling of
each interior |
10 |
| stairwell. The detector shall be installed on the ceiling,
at |
11 |
| least 6 inches from the wall, or on a wall located between 4 |
12 |
| and 6
inches from the ceiling.
|
13 |
| (d) It shall be the responsibility of the owner of a |
14 |
| structure to supply
and install all required detectors. The |
15 |
| owner shall be responsible for
making reasonable efforts to |
16 |
| test and maintain detectors in common
stairwells and hallways. |
17 |
| It shall be the responsibility of a tenant to
test and to |
18 |
| provide general maintenance for the detectors within the
|
19 |
| tenant's dwelling unit or rooming unit, and to notify the owner |
20 |
| or the
authorized agent of the owner in writing of any |
21 |
| deficiencies which the
tenant cannot correct. The owner shall |
22 |
| be responsible for providing one
tenant per dwelling unit with |
23 |
| written information regarding detector
testing and |
24 |
| maintenance.
|
25 |
| The tenant shall be responsible for replacement of any |
26 |
| required batteries
in the smoke detectors in the tenant's |
|
|
|
HB5821 Engrossed |
- 5 - |
LRB096 20660 DRJ 36377 b |
|
|
1 |
| dwelling unit, except that the owner
shall ensure that such |
2 |
| batteries are in operating condition at the time
the tenant |
3 |
| takes possession of the dwelling unit. The tenant shall provide
|
4 |
| the owner or the authorized agent of the owner with access to |
5 |
| the dwelling
unit to correct any deficiencies in the smoke |
6 |
| detector which have been
reported in writing to the owner or |
7 |
| the authorized agent of the owner.
|
8 |
| (e) The requirements of this Section shall apply to any |
9 |
| dwelling unit
in existence on July 1, 1988, beginning on that |
10 |
| date. Except as provided
in subsections (f) and (g), the smoke |
11 |
| detectors required in such dwelling
units may be either battery |
12 |
| powered or wired into the structure's AC power
line, and need |
13 |
| not be interconnected.
|
14 |
| (f) In the case of any dwelling unit that is newly |
15 |
| constructed,
reconstructed, or substantially remodelled after |
16 |
| December 31, 1987, the
requirements of this Section shall apply |
17 |
| beginning on the first day of
occupancy of the dwelling unit |
18 |
| after such construction, reconstruction or
substantial |
19 |
| remodelling. The smoke detectors required in such dwelling
unit |
20 |
| shall be permanently wired into the structure's AC power line, |
21 |
| and if
more than one detector is required to be installed |
22 |
| within the dwelling
unit, the detectors shall be wired so that |
23 |
| the actuation of one detector
will actuate all the detectors in |
24 |
| the dwelling unit.
|
25 |
| In the case of any dwelling unit that is newly constructed,
|
26 |
| reconstructed, or substantially remodeled on or after January |
|
|
|
HB5821 Engrossed |
- 6 - |
LRB096 20660 DRJ 36377 b |
|
|
1 |
| 1, 2011, smoke detectors permanently wired into the structure's |
2 |
| AC power line must also maintain an alternative back-up power |
3 |
| source, which may be either a battery or batteries or an |
4 |
| emergency generator. |
5 |
| (g) Every hotel shall be equipped with operational portable
|
6 |
| smoke-detecting alarm devices for the deaf and hearing impaired |
7 |
| of audible
and visual design, available for units of occupancy.
|
8 |
| Specialized smoke-detectors for the deaf and hearing |
9 |
| impaired shall be
available upon request by guests in such |
10 |
| hotels at a rate
of at least one such smoke detector per 75 |
11 |
| occupancy units or portions
thereof, not to exceed 5 such smoke |
12 |
| detectors per hotel.
Incorporation or connection into an |
13 |
| existing interior alarm system, so as
to be capable of being |
14 |
| activated by the system, may be utilized in lieu of
the |
15 |
| portable alarms.
|
16 |
| Operators of any hotel shall post conspicuously at the main |
17 |
| desk a
permanent notice, in letters at least 3 inches in |
18 |
| height, stating that
smoke detector alarm devices for the deaf |
19 |
| and hearing impaired are
available. The proprietor may require |
20 |
| a refundable deposit for a portable
smoke detector not to |
21 |
| exceed the cost of the detector.
|
22 |
| (h) Compliance with an applicable federal, State or local |
23 |
| law or
building code which requires the installation and |
24 |
| maintenance of smoke
detectors in a manner different from this |
25 |
| Section, but providing a level of
safety for occupants which is |
26 |
| equal to or greater than that provided by
this Section, shall |