| | 09900HB0152ham001 | - 2 - | LRB099 03752 SXM 30850 a |
|
|
| 1 | | authority be equipped with approved carbon monoxide alarms or |
| 2 | | carbon monoxide detectors, in accordance with rules adopted by |
| 3 | | the State Fire Marshal. The alarms must be powered as follows: |
| 4 | | (1) For a school designed before the effective date of |
| 5 | | this amendatory Act of the 99th General Assembly, alarms |
| 6 | | powered by batteries are permitted. In accordance with |
| 7 | | Section 17-2.11 of this Code, alarms permanently powered by |
| 8 | | the building's electrical system and monitored by any |
| 9 | | required fire alarm system are also permitted. Fire |
| 10 | | prevention and safety tax levy proceeds or bond proceeds |
| 11 | | may be used for alarms so permanently powered and |
| 12 | | monitored. |
| 13 | | (2) For a school designed on or after the effective |
| 14 | | date of this amendatory Act of the 99th General Assembly, |
| 15 | | alarms must be permanently powered by the building's |
| 16 | | electrical system or be an approved carbon monoxide |
| 17 | | detection system. An installation required in this |
| 18 | | subdivision (2) must be monitored by any required fire |
| 19 | | alarm system. |
| 20 | | (c) The State Fire Marshal shall adopt rules that (i) |
| 21 | | determine approved alarms, detectors, and systems; (ii) |
| 22 | | determine the number of alarms or detectors a school must have |
| 23 | | and where those alarms or detectors must be located; (iii) |
| 24 | | require that the alarms or detectors be in operating condition |
| 25 | | and be inspected annually; (iv) exempt a school from the |
| 26 | | requirements of this Section if they do not have or are not |
|
| | 09900HB0152ham001 | - 3 - | LRB099 03752 SXM 30850 a |
|
|
| 1 | | close to any sources of carbon monoxide; and (v) require plans, |
| 2 | | protocols, and procedures in response to the activation of a |
| 3 | | carbon monoxide alarm or carbon monoxide detection system. The |
| 4 | | State Fire Marshal may adopt any other rules necessary to |
| 5 | | administer this Section. |
| 6 | | (105 ILCS 5/34-18.49 new) |
| 7 | | Sec. 34-18.49. Carbon monoxide alarm required. |
| 8 | | (a) In this Section: |
| 9 | | "Approved carbon monoxide alarm" and "alarm" have the |
| 10 | | meaning ascribed to those terms in the Carbon Monoxide Alarm |
| 11 | | Detector Act. |
| 12 | | "Carbon monoxide detector" and "detector" mean a device |
| 13 | | having a sensor that responds to carbon monoxide gas and that |
| 14 | | is connected to an alarm control unit and approved in |
| 15 | | accordance with rules adopted by the State Fire Marshal. |
| 16 | | (b) The board shall require that each school under its |
| 17 | | authority be equipped with approved carbon monoxide alarms or |
| 18 | | carbon monoxide detectors, in accordance with rules adopted by |
| 19 | | the State Fire Marshal. The alarms must be powered as follows: |
| 20 | | (1) For a school designed before the effective date of |
| 21 | | this amendatory Act of the 99th General Assembly, alarms |
| 22 | | powered by batteries are permitted. In accordance with |
| 23 | | Section 17-2.11 of this Code, alarms permanently powered by |
| 24 | | the building's electrical system and monitored by any |
| 25 | | required fire alarm system are also permitted. Fire |
|
| | 09900HB0152ham001 | - 4 - | LRB099 03752 SXM 30850 a |
|
|
| 1 | | prevention and safety tax levy proceeds or bond proceeds |
| 2 | | may be used for alarms so permanently powered and |
| 3 | | monitored. |
| 4 | | (2) For a school designed on or after the effective |
| 5 | | date of this amendatory Act of the 99th General Assembly, |
| 6 | | alarms must be permanently powered by the building's |
| 7 | | electrical system or be an approved carbon monoxide |
| 8 | | detection system. An installation required in this |
| 9 | | subdivision (2) must be monitored by any required fire |
| 10 | | alarm system. |
| 11 | | (c) The State Fire Marshal shall adopt rules that: (i) |
| 12 | | determine approved alarms, detectors, and systems; (ii) |
| 13 | | determine the number of alarms or detectors a school must have |
| 14 | | and where those alarms or detectors must be located; (iii) |
| 15 | | require that the alarms or detectors be in operating condition |
| 16 | | and be inspected annually; (iv) exempt a school from the |
| 17 | | requirements of this Section if they do not have or are not |
| 18 | | close to any sources of carbon monoxide; and (v) require plans, |
| 19 | | protocols, and procedures in response to the activation of a |
| 20 | | carbon monoxide alarm or carbon monoxide detection system. The |
| 21 | | State Fire Marshal may adopt any other rules necessary to |
| 22 | | administer this Section.
|
| 23 | | Section 99. Effective date. This Act takes effect January |
| 24 | | 1, 2016.".
|